Power control
Fields of application
Voltage stabilization (welding stations and machines, EDM machines), temperature control (film stretchers, electric ovens), dimming (photo studios, nurseries)
Features
The APR-D series is the successor to the αB and αC products. Their functions and performance have been greatly enhanced by the incorporation of a central unit, saving space, reducing wiring and lowering cost.
Input | Main circuit | Rated voltage | Single-phase | 100/240 V AC |
Three-phase | 200 to 240 V AC ±10% (performance guarantee), ±15% (functional guarantee) 380 to 480 V AC ±10% (performance guarantee), ±15% (functional guarantee) | |||
Frequency | Single-phase | 50 Hz/ 60 Hz (automatic identification) | ||
Three-phase | 50 Hz/ 60 Hz ±2.5 Hz (Must be the same as the control circuit). | |||
Control circuit | Feeding capacity | 15 VA or less | ||
Output | Rated current (ambient temperature: 40°C) | 20A, 45A, 60A, 100A | ||
Applied load | Single-phase | Resistive load, inductive load, transformer primary control, rectifier primary control (for cycle control, resistive load (alloy) only) | ||
Three-phase | Resistive load | |||
Minimum load current | 0.5 A (at 100% of rated input voltage) | |||
Loss of generation | Single-phase | 30, 55, 70, 110 | ||
Three-phase | 75, 155, 196, 317 | |||
Control type | Waveform control method Output voltage adjustment range Input/output characteristics Control signal (automatic, manual, digital, high/low) Gradient setting Base load setting Soft start time, soft rise time, soft fall time Feedback control method (phase control only) for single-phase APR Manual/auto Switching signal for single-phase APR Sweep interval setting for three-phase APR | |||
Ambient temperature | From -10 °C to +55 °C (If +40 °C is exceeded, load current must be reduced). | |||
Storage temperature | -20 to +60 °C | |||
Ambient humidity | +5 to +95% RH (non-condensing). | |||
Environment | There must be no actions or vibrations that induce corrosive gases (sulfurized gas, ammonia gas, etc.), fine particles or insulation deterioration. Indoors, altitude up to 1000 m | |||
Insulation | Dielectric strength (between circuit and ground) | Single-phase | 2000 V AC, 1 minute | |
Three-phase | 2 kV AC, 1 minute (200 to 240 V); 2.5 kV AC, 1 minute (380 to 480 V) | |||
Insulation resistance (to earth) | 10 MΩ or more with a 500 V DC megohmmeter |
Controlling harmonics and saving energy in the plastics industry with Fuji Electric SCR power controllers
Reducing emissions and improving quality for a food manufacturer with scr power controller
Optimise lithium battery manufacturing with high precision SCR power controllers
Electrification of industrial furnaces with power controllers
Technologies
Master SCR Power Controllers with our comprehensive guide: Explore their benefits, key applications, and tips to maximize energy efficiency.
Power controller - APR-D
Reference : APR-D